ZHANG Yunfei, YE Bin, QUAN Fengyun, et al. Operation strategy and capacity optimization of Li-ion capacitor coordinated pumped storage for secondary frequency regulation[J]. Energy Storage Science and Technology, 2026, 15(9): 3722-3733.
ZHANG Yunfei, YE Bin, QUAN Fengyun, et al. Operation strategy and capacity optimization of Li-ion capacitor coordinated pumped storage for secondary frequency regulation[J]. Energy Storage Science and Technology, 2026, 15(9): 3722-3733.DOI: 10.19799/j.cnki.2095-4239.2026.0410.
Operation strategy and capacity optimization of Li-ion capacitor coordinated pumped storage for secondary frequency regulation
为提升抽蓄响应自动发电控制(automatic generation control,AGC)指令的性能与经济性,提出了一种考虑抽蓄磨损的锂电容(lithium-ion capacitor,LiC)协同抽蓄的运行策略与容量优化方法。首先,以LiC的荷电状态(state of charge,SOC)偏差、抽蓄功率变化及AGC跟踪误差最小为目标,提出了一种自适应模型预测控制(model predictive control,MPC)策略,以提升系统AGC响应性能并降低LiC能量受限导致的功率突变。然后,基于抽水蓄能机组核心部件的磨损机理,构建了以机组功率变化量及变化率为决策变量的抽蓄磨损模型。进一步,以最大化项目规划期内系统年化净收益为目标,建立了LiC的容量配置模型。最后,通过运行策略与容量配置的联合迭代,实现二者协同优化。算例结果表明,所提自适应MPC策略下,联合系统的日收益较未配置LiC提高了21.5%。采用最优容量方案可使抽蓄磨损降低16.0%,并使联合系统的年化净收益提升18.1%。
Abstract
To improve the performance and economic efficiency of pumped storage hydropower (PSH) in responding to automatic generation control (AGC) signals
a coordinated operation strategy and a capacity optimization method for a PSH-lithium-ion capacitor (LiC) hybrid system that account for the impact of PSH wear are proposed. First
an adaptive model predictive control (MPC) strategy is proposed to minimize the LiC state-of-charge deviation
PSH fluctuations
and AGC tracking errors
thereby improving the system's AGC response and mitigating power fluctuations caused by LiC energy limits. Next
based on the wear mechanisms of the core components of PSH units
a wear model is constructed using unit power variation and ramp rate as decision variables. Furthermore
a LiC-capacity-configuration model is established to maximize the system's annualized net profit over the project-planning horizon. Finally
the coordinated optimization of the operation strategy and capacity configuration is achieved through an iterative process. Case study results show that the proposed adaptive MPC strategy increases daily system profit by 21.5% compared with the case without LiC configuration. Moreover
the optimal capacity-configuration scheme reduces PSH wear by 16.0% and increases the annualized net profit of the PSH-LiC hybrid system by 18.1%.
关键词
Keywords
references
BULUT M, ÖZCAN E. How to build a state-of-the-art battery energy storage market? Challenges, opportunities, and future directions[J]. Journal of Energy Storage, 2024, 86: 111174. DOI:10.1016/j.est.2024.111174.
XU C Y, TANG Y Z, LI Q Y, et al. Supercapacitor energy storage systems for frequency regulation applications in power systems[J]. Energy Storage Science and Technology, 2025, 14(8): 3078-3089.
LIU W Y, ZHENG Y, ZHOU X, et al. Enhanced frequency regulation in pumped hydro storage integrated power systems: An innovative modeling method and GPC-PI control strategy[J]. Journal of Energy Storage, 2024, 103: 114251. DOI:10.1016/j.est.2024.114251.
WANG S, YAN H, LI J, et al. Power distribution strategy of energy storage system auxiliary secondary frequency regulation considering battery life[J]. Clean Coal Technology, 2024, 30(9): 95-101. DOI:10.13226/j.issn.1006-6772.LHX24052901.
KONG Y Y, ZHANG X, AN Y B, et al. Recent advances in preparation of MOF-derived porous carbon-based materials and their applications in anodes of lithium-ion capacitors[J]. Energy Storage Science and Technology, 2024, 13(8): 2665-2678. DOI:10.19799/j.cnki.2095-4239.2024.0050.
XU Y, LI C, REN X, et al. Research progress in low-temperature lithium-ion capacitors[J]. Chinese Journal of Engineering, 2024, 46(8): 1509-1520. DOI:10.13374/j.issn2095-9389.2023.09. 20.001.
YU L L, SI R H, CHANG Q Q, et al. Capacity allocation of BESS in secondary frequency regulation based on area control error[J]. Renewable Energy Resources, 2023, 41(8): 1129-1136. DOI:10. 3969/j.issn.1671-5292.2023.08.019.
ZHANG Y, SHEN Y, ZHU R, et al. Two-stage frequency regulation strategy of the combined heat and power plant with energy storage basing regulation indicators in northeast grid[J]. Power System Technology, 2025, 49(9): 3623-3632, I0021-I0027.
QIN H, QIN L J, BAI X C, et al. A control strategy of flywheel energy storage system participating frequency regulation with pumped storage[J]. Energy Storage Science and Technology, 2022, 11(12): 3915-3925.
DUAN X H, SUN D, ZHAO C, et al. Multi-state interval optimization strategy for energy storage clusters considering frequency regulation capability and economic benefits[J]. Automation of Electric Power Systems, 2024, 48(5): 58-67. DOI:10.7500/AEPS20230808006.
FANG F, LIU Y B, WANG B Y, et al. Optimal load allocation strategy of flywheel-thermal power coordinated secondary frequency regulation based on non-dominated sorting genetic algorithm-Ⅱ [J]. Automation of Electric Power Systems, 2024, 48(12): 79-88. DOI:10.7500/AEPS20230830008.
JING K, WU Y M, CHEN W Q, et al. Optimized allocation of electric-hydrogen hybrid energy storage capacity based on PSO-VMD[J]. Energy Storage Science and Technology, 2025, 14(12): 4644-4653.
MOU X P, CAI Q, ZHOU Y R, et al. Energy storage capacity configuration method based on deep reinforcement learning and multi-objective particle swarm optimization[J]. Energy Storage Science and Technology, 2026, 15(2): 583-590.
LI J H, WU P Y, HUANG F Q, et al. Research and application of AGC frequency regulation capacity allocation scheme for supercapacitor hybrid energy storage assisted thermal power unit[J]. Thermal Power Generation, 2025, 54(7): 101-110.
YANG D Q, WEI P. A study on the optimal capacity configuration method for secondary frequency regulation of hybrid energy storage based on wavelet transform[J]. Power System and Clean Energy, 2025, 41(10): 24-35.
ZHENG T Y, YE M H, WU Q H. Capacity allocation method for a hybrid energy storage system participating in secondary frequency regulation based on variational mode decomposition[J]. International Journal of Electrical Power & Energy Systems, 2025, 167: 110631. DOI:10.1016/j.ijepes.2025.110631.