Comparative study on the performance of a quasi-two-stage compression air-source heat pump under different participation modes of the thermal storage unit
Energy Storage Test\: Methods and Evaluation|更新时间:2026-08-26
|
Comparative study on the performance of a quasi-two-stage compression air-source heat pump under different participation modes of the thermal storage unit
Energy Storage Science and TechnologyVol. 15, Issue 8, Pages: 3356-3365(2026)
SONG Chunyu, LI Yong, MU Wenyi, et al. Comparative study on the performance of a quasi-two-stage compression air-source heat pump under different participation modes of the thermal storage unit[J]. Energy Storage Science and Technology, 2026, 15(8): 3356-3365.
SONG Chunyu, LI Yong, MU Wenyi, et al. Comparative study on the performance of a quasi-two-stage compression air-source heat pump under different participation modes of the thermal storage unit[J]. Energy Storage Science and Technology, 2026, 15(8): 3356-3365.DOI: 10.19799/j.cnki.2095-4239.2026.0266.
Comparative study on the performance of a quasi-two-stage compression air-source heat pump under different participation modes of the thermal storage unit
To address problems such as heating performance degradation
high compressor discharge temperature
and insufficient system stability in air-source heat pumps operating at low temperatures in cold regions
an experimental quasi-two-stage compression air-source heat pump system coupled with a thermal storage unit was built. Two operation modes were compared: Mode A (main refrigerant subcooled by the thermal storage unit) and Mode B (main refrigerant not subcooled by the thermal storage unit). Experiments were conducted at ambient temperatures of -25℃
-15℃
and -5℃ to evaluate the heating capacity
coefficient of performance (COP)
compressor parameters
refrigerant flow distribution
exergy efficiency
and variable-load stability. The results showed that
compared with Mode A
the heating capacity of Mode B was increased by 2.93%
2.14%
and 15.01%
and the COP was increased by 9.39%
5.60%
and 6.53% at -25℃
-15℃
and -5℃
respectively. At -25℃
the discharge temperature and pressure were reduced by 28.5℃ and 0.24 MPa
respectively. Refrigerant distribution revealed that Mode B distributed more refrigerant to the economizer and thermal storage unit vapor-injection branches
with flow rates increasing by 32.81%—49.18% and 33.84%—38.76%
respectively
strengthening low-temperature vapor injection. Exergy analysis indicated that the total exergy loss of Mode B was reduced by 10.31%
4.89%
and 3.48%
and the exergy efficiency was improved by 5.91%
1.90%
and 8.79%. Mode B also remained stable under variable load at -25℃. The participation mode of the thermal storage unit markedly affects low-temperature and thermodynamic performance. Mode B
which does not subcool the main flow
reduces flow resistance and irreversible loss
optimizes refrigerant distribution
and improves low-temperature adaptability and overall performance
thereby providing experimental support and a technical reference for the optimal design of air-source heat pumps in severe cold regions.
XIAO Y M, ZHANG C, FU X Z. Experimental studies on the operation of air source heat pump in extreme winter weather[J]. Acta Energiae Solaris Sinica, 2010, 31(12): 1580-1584.
ZOU D Q, MA X F, LIU X S, et al. Experimental research of an air-source heat pump water heater using water-PCM for heat storage[J]. Applied Energy, 2017, 206: 784-792. DOI:10.1016/j.apenergy.2017.08.209.
LIU H J, GU Z L, LING T T. Experimental study on air conditioning system with heat recovery of compressor discharge gas[J]. Journal of Refrigeration, 2005, 26(1): 1-4. DOI:10.3969/j.issn.0253-4339.2005.01.001.
LIU Z B, LOU F F, QI X, et al. Enhancing heating performance of low-temperature air source heat pumps using compressor casing thermal storage[J]. Energies, 2020, 13(12): 3269. DOI:10.3390/en13123269.
ZHU C H, YAN S B, DONG X D, et al. Exergy analysis of phase-change heat-storage coupled solar heat pump heating system[J]. Materials, 2021, 14(19): 5552. DOI:10.3390/ma14195552.
MA S X, JIANG Y M, WEN B, et al. Experimental study on the performance of the ashp with phase change heat storage evaporator[J]. Acta Energiae Solaris Sinica, 2015, 36(3): 604-609.
XIE H, MA S X, YIN J G, et al. Experimental study of performance optimization of phase change heat storage evaporator type air-source heat pump[J]. Acta Energiae Solaris Sinica, 2017, 38(8): 2253-2257.
YAN Z B, MA S X, LI X G. Design of solar energy-phase change heat storage evaportive air-source heat pumps compound heating system[J]. Renewable Energy Resources, 2018, 36(2): 209-214. DOI:10.3969/j.issn.1671-5292.2018.02.008.
FAN W Y, JIANG L L, CAI B R, et al. Operation analysis of air source phase change energy storage compound heat pump system[J]. Renewable Energy Resources, 2021, 39(9): 1175-1182. DOI:10.3969/j.issn.1671-5292.2021.09.006.
YANG Y, LI F L, LI R R. Energy and exergy analyses of solar booster-assisted ejector refrigeration system[J]. Science Technology and Engineering, 2020, 20(6): 2272-2278. DOI:10.3969/j. issn.1671-1815.2020.06.023.